Evolution DX2 series Bedienungsanleitung Seite 2

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 11
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 1
Rain Master Irrigation Systems DX2 User Manual
Appendix B: Current Monitor Page 255
Current Limit Detection
When a current limit is detected, the controller performs the
following actions:
1. If the limit is for a station, operation of the station is
immediately terminated.
2. The problem is listed as a warning/alarm.
3. The controller advances to the next station in the current
program (if applicable).
4. The station is entered in a "condemned" list. No
watering occurs for those stations in the "condemned
list" until the problem is corrected.
To remove a station from the bad list, delete the problem from
the warning report, refer to Chapter 10.
Warning:
To properly monitor current levels:
You must enter minimum and
maximum current levels to be
monitored by the system.
When setting limits, the controller
automatically sums limits when
multiple stations and/or the Master
Valve are on. For example, assume
station 1 has a .2 Amps limit and the
Master Valve has a .4 Amps limit.
When both are on, the controller
adds (.2 Amps) + (.4 Amps) = .6
Amps. The measured value is then
compared to .6 Amps.
Current monitoring must be enabled.
Seitenansicht 1
1 2 3 4 5 6 7 ... 10 11

Kommentare zu diesen Handbüchern

Keine Kommentare